
Below is what I think I learnt on the third day of my introduction to electricals course courtesy of Able Skills in Dartford. I must emphasise that I am neither connected in any way with Able Skills nor receiving any form of payment from them. I’m simply undertaking the course and blogging about it simultaneously, which may be foolish since I would like to complete it before they discover my blog. I have been a little critical but mainly, luckily for both them and me, I’ve been praising the disarmingly engaging manner on which Alan and Steve have been teaching us. Their attention to detail has been impressive and their good humour in endless supply. I’ve done all sorts of education (as you can tell from my strapline) but this crew has easily created the best atmosphere of any class I’ve ever been in. As a group of students, we’re about as eclectic as you can get but have gelled nicely, even with yours truly! Classmates help each other out. There is shared auto-didactivism but I’d better stop there before I am accused on hyperpolysyllabicsesquipedalianism. Confess to being unsure of correct spelling of 8th syllable in that word but I don’t think spoils the joke!
Back to what I learnt today… first up we were told that the picture on page 79 of the On Site Guide (which I’m going to call the “OSG” from now on because you can never have enough TLAs) was an acceptable way to perform the CPC CONTINUITY TEST (the picture includes a temporary link between line and the distribution board’s CPC) but it is less safe than disconnecting the circuit’s line and CPC from the distribution board and joining them with a connector block because you might forget to remove the temporary link and cause a fire.
When terminating two conductors together, never twist them together because one of then might well snap when you screw the termination down. Instead push them in side by side and screw down into each of them from above. This is a Part P question.
The order of the tests was finalised today but remained to be fine tuned next week.
Earthing Systems
There are five wiring systems. Three are legal in a public supply and the other two are used in private commercial systems, such as coal mines.
Legend:
T – Earth
N – Neutral
C – Combined
S – Separate
The first system is TN-S. This has two cores, live and neutral. They are protected by an armored shell which is also earth. The wiring diagram for this system is shown on page 15 of the OSG.
All new properties since about 35 years ago are supplied via a different system, the TN-C-S, which is also called protected multiple earthing (PME). This system only has one core, which is live. Its armoured shell is both earth and neutral.
The third system is called TT. There are two cores, live and neutral, but no earth. The earth has to be built manually at the domestic property. This is now rare in England and Wales and is mainly found in rural areas. These cables are always strung up overhead on wooden posts. This saves the trouble of finding them in fields and avoids farmers getting electrocuted.
Maximum Permitted Impedances
Max Ze on TN-S = 0.8Ω
Max Ze on TN-C-S = 0.35Ω
Max Ze on TT = 200Ω
TT is an unstable system. Ze on TT will change according to the climactic condition of the ground. 5-50Ω is the expected figure. TT systems always had RCDs because they are so inefficient. However, that might not be a 30mA RCD. It might be 100mA. That does not comply with the 17th Edition. The OSG recommends using RCBOs with a TT system. You might use a 100mA RCD before a life saving 30mA RCD. That is inconvenient though because a fault can shut down the entire house.
Incidentally, do not trust a £10 stud detector.
A £100 stud detector would be trustworthy.
You need to be able to identify the three different earthing systems.
In Able Skills’ building the Ze measurements are artificially high because there is a second distribution board between the original one and the testing bays.
If the earthing resistance is above the permitted maximum, it must be reported.
If you need to identify the location of underground services (gas and water pipes), use a decent metal detector. With a TT system, the first thing to do is to look for the overhead cable. The second thing to do is to locate the earth conductor.
A split load consumer system or RCBOs can be used with any system. Don’t buy £5 RCBOs from the internet because at that price they are bound to be dodgy. They’ll be type C or D, which we don’t want.
Don’t forget to never pay cash for anything. Set up a trade account at a wholesalers. Persuade them to give you a discount from the start of the account.
Multi-function testers are made by AVO (the megger), FLUKE (ROBIN), DI-LOG, METREL, KEWTECH and INSTROTECH. You might get a used model from a calibrater.
There is no maximum for R1 or R2. The maximum Zs is limited for BSEN 60898 MCB and BSEN 61009 RCBOs (B type). See table 2D on page 103 of the OSG. We will only use the breakers listed on page 49 of the Electricians Guide to the Building Regulations.
6A – 6.18Ω
10A – 3.71Ω
16A – 2.32Ω
20A – 1.85Ω
32A – 1.16Ω
40A – 0.93Ω
45A – 0.82Ω
You can see a pattern above. As the amps doubles, the impedance halves. Zs has to be below the tabulated maximums. You don’t need to remember these figures because they are in the table but they can be
calculated from the first two sets of figures in the table anyway. Just to complicate matters, there is a different set of values for the design maximums. The measured maximums listed above are multiplied by 1.25 {I’m unsure about this multiplier’s accuracy} to give you a safety margin. As domestic installers we just need to know that there are two sets of values, one for design and one for testing.
A verification inspection confirms that an installation complies with the wiring regulations. The regulations are considered, by the Health & Safety Executive, to comply with the Electricity at Work Regulations 1989.
People become blase about the risks we were warned. Later I realised that I had already become blase, when not paying attention properly to my crocodile clips during a live test. Made a mental note to always retain my ultra caution. My risk adversity as my friend Anita would call it.
Live working should be avoided unless it is unreasonable not to do so.
Isolation procedure
1. Check it is ok to isolate the circuit
2. Lock off the circuit and tag it.
3. Check that there is no dangerous voltage present.
4. Check the voltage again.
A single person our a single organisation must be responsible for the design.
Inspection must be more than just visual. Touch and smell can be employed too.
When testing R1 + R2, always record the highest figure from each of the loads in the circuit. This will be the last ceiling rose for example. Always do the continuity tests first. Always put the line probe on last and remove it first to prevent the neutral crocodile clip from waving around the line contact.
Put the highest short circuit current on the test form.
RCD Testing
Page 91/93 of the OSG deals with this. You have to test the 30mA RCD or RCBO, even if it its brand new. Under fault conditions the RCD will take differing times rio detect the fault. The resulting delay in shutting down the power will vary according to where it is in the cycle. Domestic electricity is supplied at 50Hz (50 cycles per second).
Until very recently, seven tests were performed to test an RCD. One tester (an AVO megger) has conflated the first two tests. Doubtless the updated models of the others will follow that lead. The first two tests are duplicitous.
The seven 30mA RCD tests are:
1. 15mA @ 0°
2. 15mA @ 180°
This establishes that the RCD will not trip at faults below the danger threshold. The RCD should either not trip or else trip in approximately two seconds.
3. 30mA @ 0°
4. 30mA @ 180°
The RCD should operate at
5. 150mA @ 0°
6. 150mA @ 180°
The RCD should operate at 40mS (0.04S). This is much faster than a fuse or a circuit breaker. It gets faster as the current goes up.
7. Push the RCD test button – this ensures that the mechanism hasn’t seized up.
An auto RCD test is exactly the same but quicker. only record the highest figure from each pair of results.
Ramp Test
Another test, which isn’t required for the paperwork but is nonetheless a useful fault finding test is the ramp test. Not all multi-function testers can do the ramp test. It ramps up the current to the RCD t